Product Overview
Construction Details
CONDUCTOR
INSULATION
OUTER SHIELD MATERIAL
OUTER JACKET MATERIAL
Electrical Characteristics
ELECTRICALS
VOLTAGE
Mechanical Characteristics
TEMPERATURE
BEND RADIUS
Standards and Compliance
Type EX Thermocouple, 1 Pair 16AWG (Solid) Chromel+Constantan, PVC Insulation Pur, Red Color Code, Overall Beldfoil® Shield, Purple PVC Outer Jacket, PLTC-ER ITC-ER CMG AWM 2464 SUN RES
Suitable Applications | Industrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, …),low voltage digital control (24v, …),Thermocouple, distributed control system (DCS),programmable logic controller (PLC) |
---|
Element | Number of Element | AWG | Stranding | Material |
---|---|---|---|---|
Pair(s) | 1 | 16 | Solid | Chromel & Constantan |
Element | Material | Thickness | Nom. Insulation Diameter | Color Code |
---|---|---|---|---|
Pair(s) | PVC – Polyvinyl Chloride | 0.021 in | 0.093 | Purple & Red |
Shield Type | Material | Coverage | Drainwire Type |
---|---|---|---|
Tape | Bi-Laminate (Alum+Poly) | 100% | 18 AWG (7×26) TC |
Material | Thickness | Nom. Diameter | Ripcord |
---|---|---|---|
PVC – Polyvinyl Chloride | 0.037 in | 0.264 in | Yes |
Cable Diameter (Nominal) | 0.264 in |
---|
Element | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Shield |
---|---|---|
Pair(s) | 25 pF/ft | 51 pF/ft |
Table Notes | Conductor DCR (Nom): 165 Ohm/1000ft (Chromel), 121 Ohm/1000ft (Constantan) |
---|---|
Nom Outer Shield DCR | 38 Ohm/1000ft |
UL Voltage Rating |
---|
300 V (PLTC-ER, CMG, UL AWM 2464), 150 V (ITC-ER) |
UL Rating | Operating |
---|---|
105°C | -30°C to +105°C |
Stationary Min. | Installation Min. |
---|---|
2.5 in | 2.6 in |
Max. Pull Tension | 83 lbs |
---|---|
Bulk Cable Weight | 38 lbs/1000ft |
Environmental Suitability | Indoor/Outdoor, Indoor, Outdoor, Sunlight Resistance |
---|---|
Flammability / Fire Resistance | UL1685 (FT4 Loading), FT4, T-29-520, 1202 |
NEC / UL Compliance | Article 725, Article 727, Article 800, CMG, PLTC-ER, ITC-ER |
AWM Compliance | 2464 |
CEC / C(UL) Compliance | CMG |
European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
APAC Compliance | China RoHS II (GB/T 26572-2011) |
Other Standard Compliance(s) | ISA MC 96.1-1982 Type EX |