Standard Technical Specifications:
| Standard | IEC60076 & SEC | |
| Rated frequency | 60 HZ | |
| Connection and vector group | Dyn11* | |
| Ambient temperature | 55 °C | |
| Max temperature rise | Top oil | 45 °C |
| Average winding | 50 °C | |
| Type of cooling | ONAN | |
| HV tapping | Off-circuit tap changer 5 positions | ± 2×2.5 * % |
| Rated Power | HV | LV | NO Load Loss | Load Loss | Z% |
|---|---|---|---|---|---|
| KVA | V | V | W | W | % |
| 300 | 13.8 | 0.4 | 520 | 3200 | 4 |
| 500 | 13.8 | 0.4 | 750 | 4700 | 5 |
| 1000 | 13.8 | 0.4 | 1100 | 9000 | 6 |
| 1500 | 13.8 | 0.4 | 1700 | 14000 | 6 |
Note : Custom specifications and requirements can be designed and manufactured upon request.





Reviews