Standard Technical Specifications:
| Standard | IEC60076 & SEC | |
| Rated frequency | 60 HZ | |
| Connection and vector group | Dyn11* | |
| Ambient temperatureerature | 55 °C | |
| Max temperature rise | Top oil | 45 °C |
| Average winding | 50 °C | |
| Type of cooling | ONAN | |
| HV tapping | Off-circuit tap changer 5 positions | ± 2×2.5 * % |
| Rated Power | HV | LV | NO Load Loss | Load Loss | Z% | Width | Depth | Height |
|---|---|---|---|---|---|---|---|---|
| KVA | V | V | W | W | % | mm | mm | mm |
| 300 | 13.8 | 0.4 | 520 | 3200 | 4 | 1700 | 1400 | 1600 |
| 500 | 13.8 | 0.4 | 720 | 4700 | 5 | 1700 | 1400 | 1600 |
| 1000 | 13.8 | 0.4 | 1100 | 9000 | 6 | 1900 | 1600 | 1900 |
| 1500 | 13.8 | 0.4 | 1700 | 14000 | 6 | 1920 | 1700 | 2000 |
| 300 | 33 | 0.4 | 520 | 3200 | 4 | 1700 | 1400 | 1600 |
| 500 | 33 | 0.4 | 750 | 4700 | 5 | 1700 | 1400 | 1600 |
| 1000 | 33 | 0.4 | 1100 | 9000 | 6 | 1900 | 1600 | 1900 |
| 1500 | 33 | 0.4 | 1700 | 14000 | 6 | 1920 | 1700 | 2000 |
Note : Custom specifications and requirements can be designed and manufactured upon request.