Standard Technical Specifications:
Standard | IEC60076 & SEC | |
Rated frequency | 60 HZ | |
Connection and vector group | Dyn11* | |
Ambient temperature | 55 °C | |
Max temperature rise | Top oil | 45 °C |
Average winding | 50 °C | |
Type of cooling | ONAN | |
HV tapping | Off-circuit tap changer 5 positions | ± 2×2.5 * % |
Rated Power | HV | LV | NO Load Loss | Load Loss | Z% | Width | Depth | Height |
---|---|---|---|---|---|---|---|---|
KVA | V | V | W | W | % | mm | mm | mm |
100 | 13.8 | 0.4 | 250 | 1500 | 4 | 1350 | 900 | 1450 |
200 | 13.8 | 0.4 | 380 | 2200 | 4 | 1450 | 1100 | 1700 |
300 | 13.8 | 0.4 | 520 | 3200 | 4 | 1450 | 1100 | 1700 |
100 | 33 | 0.4 | 250 | 1500 | 4 | 1350 | 900 | 1450 |
200 | 33 | 0.4 | 380 | 2200 | 4 | 1450 | 1100 | 1700 |
300 | 33 | 0.4 | 520 | 3200 | 4 | 1450 | 1100 | 1700 |
Note : Custom specifications and requirements can be designed and manufactured upon request.